Chilled water systems
Ceiling cassette 4-pipe-system
Series DKT-4
Ceiling cassette 4-pipe-system
REMKO
REMKO Hexaeda

REMKO DKT-4


       
For increasing please click.




REMKO DKT-4


Cassettes for heating and air conditioning equipment

The hot indoor air is taken in via an internal, centred, regenerative air filter. The four-sided, special diffuser cover permits air distribution on two, three, or four sides under the ceiling. The low-noise radial fan, which can be adjusted in three stages, permits the optimum adaptation of the air volume to the existing conditions. The heat exchangers are available in a copper-aluminium design for media temperatures up to 80°C. In the standard version, the devices are equipped with a condensate pump. Optionally, fresh air can be supplied or adjacent rooms can be cooled. For regulation on the medium side, a "Cooling" valve subassembly is included in delivery for the standard version.

  • The ideal solution for optically discreet air conditioning
  • Compact dimensions in Euroraster format
  • Low-noise device operation
  • Servicing-friendly device structure
  • Air outlet with adjustable slats
  • Built-in condensate pump (pump delivery of up to 550 mm)
  • Valve subassembly with connecting pipes in the standard version
  • Extensive accessories available






 
Product(s) fade in/fade out:
DKT 20-4DKT 20-4DKT 50-4DKT 50-4DKT 110-4DKT 110-4

 Unit type     Unit     DKT 20-4    DKT 50-4    DKT 110-4 
 Cooling capacitykW  2,00  4,00  9,80 
 Heating capacitykW  2,00  4,00  13,30 
 Nominal air volume per stagem³/h  360/450/670  470/600/850  700/1220/1750 
 Sound pressure level per stagedB(A)  11/18/38  34/39/45  28/40/50 
 Power supplyV/Hz  230/1~/50 
 Electr. nominal power consumptionkW  0,07  0,11  0,18 
 Electr. nominal current consumptionA  0,38  0,60  1,00 
 Operating medium  Water, max. 35%, Ethylenglykol, max. 35%, Prophylenglykol 
 Operation pressure, max.kPa  600,00 
 Nominal medium flow (heating)m³/h  0,39  0,60  1,00 
 Nominal medium flow (heating coil)m³/h  0,39  -  - 
 Nominal medium flow (cooling)m³/h  0,34  0,69  1,69 
 Nominal pressure loss, internal heating coilkPa  14,00  12,00  10,00 
 Nominal pressure loss, internal coolingkPa  8,00  16,00  30,00 
 Nominal pressure loss of valvekPa  1,70  7,60  15,80 
 Medium volume cooling coil / heating coill  0,60  1,10  2,10 
 Medium connections (heating coil)Zoll  1/2  1/2  3/4 
 Medium connections (cooling coil)Zoll  3/4  3/4  1 
 Dimensions grille h/w/dmm  30/720/720  30/720/720  30/960/960 
 Dimensions ceiling cassette h/b/tmm  298/575/575  289/575/575  298/825/825 
 Weight ceiling cassette / grillekg  19,00/2,50  20,00/2,50  46,00/5,00 
 Series color  white 
 part number  1611306 1611326 1611356 
 Technical/operating instructions    PDF     -    -    - 
 accessories list accessories list  accessories listaccessories listaccessories list
 spare parts list spare parts list  spare parts listspare parts listspare parts list
Notice
Notice
We reserve the right to make technical changes. No responsibility is assumed for the correctness of this information.

Pfeil back  |  Pfeil Beginning of page  |  drucken print page
Home  |  REMKO sitemap  |  Contact  |  Imprint  |  Versandkosten
REMKO info portal > Products > Chilled water systems > Ceiling cassette 4-pipe-system > REMKO DKT-4