REMKO DKT-4 SERIES Ceiling cassettes as 4-pipe system

REMKO DKT-4 SERIES Ceiling cassettes as 4-pipe system
Ceiling cassettes for heating and cooling

The warm room air is suctioned in a centred manner via an internal regenerative air filter. The four-sided special diffuser cover allows two, three or four sided air distribution below the ceiling. The three-stage low-noise radial fan allows the optimal adaptation of the airflow volume to prevailing conditions. The copper-aluminium heat exchangers are designed for medium temperatures of up to 80°C. The units are fitted as standard with a condensate pump. Optionally, fresh air can be blown in or adjoining rooms can also be cooled. A "cooling" valve assembly is supplied as standard for medium control. The control of the heating circuit can be adapted to the unit.

  • The ideal solution for optically discreet air-conditioning
  • Compact dimensions in standard European grid format
  • Low-noise unit operation
  • Service-friendly unit structure
  • Air outlet with adjustable fins
  • Installed condensate pump (up to 550 mmWS)
  • "Cooling" valve subassembly with connecting pipes 
Regulation

Ceiling mounted cassettes for insertion into false ceilings are operated using a room temperature control or a precision room temperature control, either individually or in groups. The elegant and functional controls can be integrated into any wall decoration. The operating panel has a selector switch for the operating mode and the fan speed, a main switch, and a temperature controller for setting the desired room temperature.


Technical data
VariantDKT 21-4DKT 51-4DKT 71-4
Cooling capacity2.20 kW 4.10 kW 6.70 kW
Heating capacity1.90 kW 6.80 kW 11.50 kW
Air flow rate speed settings360/450/660 m³/h 485/625/900 m³/h 500/825/1160 m³/h
Sound pressure level per speed setting23/28/38 dB(A) 33/39/48 dB(A) 28/37/44 dB(A)
Power supply230/1~/50 230/1~/50 230/1~/50
Electrical nominal power consumption60 W90 W90 W
Electrical nominal current consumption0.27 A0.41 A0.46 A
Operation pressure max. agent1400 kPa1400 kPa1400 kPa
Nominal volume flow rate of medium, cooling0.4 m³/h 1.1 m³/h 1.52 m³/h
Nominal flow rate, medium, heating0.1 0.6 0.99
Nominal pressure loss, internal cooling13.7 kPa13.1 kPa23.2 kPa
Nominal pressure loss, internal heating coil31.4 kPa29.2 kPa13.6 kPa
Condensate drainage connection16 mm16 mm16 mm
Series colourweiß weiß weiß
Cover dimensions, H/W/D30/720/720 mm 30/720/720 mm 30/960/960 mm
Weight21.5 kg24.5 kg26 kg

Accessories / Spare parts

Downloads
Language
Pictures
REMKO DKT 21-4 jpg, 240,957,000.0
Assembly drawings
REMKO DKT 21-4 jpg, 57,850,000.0
Cooling load calculation for air-conditioners

The following rule of thumb applies when calculating the cooling capacity:
Approximately 30 W of cooling capacity are required per cubic meter. The cooling capacity for a room with a surface area of 28 m2 and height of 2.5 m can be calculated as follows:

28 m2 x 2,5 m x 30 W/m3 = 2.100 Watt (2,1 kW)

We recommend that you always calculate the cooling capacity for the room precisely.

Cooling load calculation Calculate required cooling capacity
Cooling load calculation