REMKO DKT-4 SERIES Ceiling cassettes as 4-pipe system

Variant EDV-Nr. Cooling capacity
DKT 21-4 1611302 2,2 kW
DKT 51-4 1611322 4,1 kW
DKT 71-4 1611342 6,7 kW

Variant

REMKO DKT-4 SERIES Ceiling cassettes as 4-pipe system

Ceiling cassettes for heating and cooling

The warm room air is suctioned in a centred manner via an internal regenerative air filter. The four-sided special diffuser cover allows two, three or four sided air distribution below the ceiling. The three-stage low-noise radial fan allows the optimal adaptation of the airflow volume to prevailing conditions. The copper-aluminium heat exchangers are designed for medium temperatures of up to 80°C. The units are fitted as standard with a condensate pump. Optionally, fresh air can be blown in or adjoining rooms can also be cooled. A "cooling" valve assembly is supplied as standard for medium control. The control of the heating circuit can be adapted to the unit.

  • The ideal solution for optically discreet air-conditioning
  • Compact dimensions in standard European grid format
  • Low-noise unit operation
  • Service-friendly unit structure
  • Air outlet with adjustable fins
  • Installed condensate pump (up to 550 mmWS)
  • "Cooling" valve subassembly with connecting pipes 

Regulation

Ceiling mounted cassettes for insertion into false ceilings are operated using a room temperature control or a precision room temperature control, either individually or in groups. The elegant and functional controls can be integrated into any wall decoration. The operating panel has a selector switch for the operating mode and the fan speed, a main switch, and a temperature controller for setting the desired room temperature.


Technical data

VariantDKT 21-4DKT 51-4DKT 71-4
Cooling capacity2,2 kW4,1 kW6,7 kW
Heating capacity1,9 kW6,8 kW11,5 kW
Nominal air volume per stage360/450/660 m³/h485/625/900 m³/h500/825/1160 m³/h
Sound pressure level per stage23/28/38 dB(A)33/39/48 dB(A)28/37/44 dB(A)
Sound power level per stage32/37/47 dB(A)42/48/57 dB(A)37/43/48 dB(A)
Power supply230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz
Electr. nominal power consumption60 W90 W90 W
Electr. nominal current consumption0,27 A0,41 A0,46 A
Operation pressure, max.1400 kPa1400 kPa1400 kPa
Nominal medium flow0,40 m³/h1,10 m³/h1,52 m³/h
Nominal medium flow (heating)0,10 m³/h0,60 m³/h0,99 m³/h
Nominal pressure loss, internal ³)13,7 kPa13,1 kPa23,2 kPa
Nominal pressure loss, internal heating coil31,4 kPa29,2 kPa13,6 kPa
Condensate drainage connection16 mm16 mm16 mm
Dimensions grille h/w/d30/720/720 mm30/720/720 mm30/960/960 mm
Dimensions h/w/d298/570/570 mm298/570/570 mm298/825/825 mm
Weight21,5 kg22,5 kg44,6 kg
Series colorweiß weiß weiß
Protection classX0 X0 X0

Accessories / Spare parts

Variant
Loading ...
Loading ...

Downloads

Variant
Language
Pictures
REMKO DKT 21-4 jpg, 240,957,000.0
Assembly drawings
REMKO DKT 21-4 jpg, 57,850,000.0

Cooling load calculation for air-conditioners

The following rule of thumb applies when calculating the cooling capacity:
Approximately 30 W of cooling capacity are required per cubic meter. The cooling capacity for a room with a surface area of 28 m2 and height of 2.5 m can be calculated as follows:

28 m2 x 2,5 m x 30 W/m3 = 2.100 Watt (2,1 kW)

We recommend that you always calculate the cooling capacity for the room precisely.

Cooling load calculation Calculate required cooling capacity