REMKO KWD EC COANDA SERIES Ceiling cassettes with 360-degree air outlet

Variant EDV-Nr. Cooling capacity
KWD 25 EC Coanda (standard filter) 1611950 2,6 kW
KWD 25 EC Coanda (EPA filter) 1611964 1,5 kW
KWD 35 EC Coanda (standard filter) 1611952 3,2 kW
KWD 35 EC Coanda (EPA filter) 1611966 1,9 kW
KWD 45 EC Coanda (standard filter) 1611954 4,4 kW
KWD 45 EC Coanda (EPA filter) 1611968 2,5 kW
KWD 55 EC Coanda (standard filter) 1611956 5,2 kW
KWD 55 EC Coanda (EPA filter) 1611970 3,0 kW
KWD 70 EC Coanda (standard filter) 1611958 6,9 kW
KWD 85 EC Coanda (standard filter) 1611960 8,4 kW
KWD 85 EC Coanda (EPA filter) 1611974 4,3 kW
KWD 100 EC Coanda (standard filter) 1611962 9,7 kW
KWD 100 EC Coanda (EPA filter) 1611976 4,5 kW

Variant

REMKO KWD EC COANDA SERIES Ceiling cassette with 60-degree air outlet

Ceiling cassettes with EC fans and Coanda screen

KWD EC Coanda ceiling cassettes use the physical properties of flowing air to evenly air-condition a room. Due to the specially designed unit cover, the air outlet is located at a small distance parallel to the ceiling, which creates a vacuum and increases the range. The flowing air thus falls into the room only slowly and draught-free.

Compared to conventional systems, a more even air distribution is possible with the Coanda screen. A significantly more pleasant feelgood climate is created without drafts.

EPA filter for air cleaning

As an option, the units can be equipped with an EPA filter (high-performance particle filter), which can meet particularly high demands on room air quality. This filters out about 99.5% of all suspended particles from the air, including pollen, mites, smoke particles and bacteria. This enables a particularly high level of air purity.

Areas of application of the EPA filter

  • Medical parctices
  • Clean rooms for measuing technology
  • Laboratories
  • Rooms with increased air quality requirements

Air distribution with standard screen

Air distribution with Coanda screen


Technical data

VariantKWD 25 EC Coanda (standard filter)KWD 25 EC Coanda (EPA filter)KWD 35 EC Coanda (standard filter)KWD 35 EC Coanda (EPA filter)KWD 45 EC Coanda (standard filter)KWD 45 EC Coanda (EPA filter)KWD 55 EC Coanda (standard filter)KWD 55 EC Coanda (EPA filter)KWD 70 EC Coanda (standard filter)KWD 85 EC Coanda (standard filter)KWD 85 EC Coanda (EPA filter)KWD 100 EC Coanda (standard filter)KWD 100 EC Coanda (EPA filter)
Cooling capacity2,6 kW1,5 kW3,2 kW1,9 kW4,4 kW2,5 kW5,2 kW3,0 kW6,9 kW8,4 kW4,3 kW9,7 kW4,5 kW
Heating capacity3,7 kW2,0 kW4,1 kW2,4 kW5,4 kW3,1 kW6,8 kW3,9 kW8,7 kW11,2 kW5,7 kW12,3 kW5,9 kW
Nominal air volume per stage180/220/320/390/440 m³/h122/133/194/236/267 m³/h220/320/390/440/520 m³/h133/194/236/267/316 m³/h215/343/397/566/684 m³/h141/225/261/372/449 m³/h229/606/665/793/974 m³/h147/390/428/510/626 m³/h385/610/700/780/1030 m³/h395/835/1057/1258/.. m³/h222/469/594/722/890 m³/h393/1057/1157/1380/. m³/h222/570/623/744/904 m³/h
Sound pressure level per stage20,8/21/23/25/27 dB(A)20,8/21/23/25/27 dB(A)21/23/25/27/33 dB(A)21/23/25/27/33 dB(A)22/226/29/37/42 dB(A)22/26/29/37/42 dB(A)21/35/38/42/47 dB(A)21/35/38/42/47 dB(A)28/29/30/34/37 dB(A)27/34/43/45/50 dB(A)24/34/43/45/50 dB(A)28/45/46/48/53 dB(A)24/45/46/48/53 dB(A)
Power supply230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz
Electr. nominal power consumption10 W10 W20 W20 W40 W40 W60 W60 W40 W110 W110 W120 W120 W
Electr. nominal current consumption0,09 A0,09 A0,13 A0,13 A0,22 A0,22 A0,33 A0,33 A0,22 A0,54 A0,54 A0,62 A0,62 A
Operation pressure, max.1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa1400 kPa
Medium connections3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch3/4 inch
Nominal medium flow0,45 m³/h0,45 m³/h0,55 m³/h0,55 m³/h0,78 m³/h0,78 m³/h0,91 m³/h0,91 m³/h0,98 m³/h1,45 m³/h1,45 m³/h1,66 m³/h1,66 m³/h
Nominal pressure loss, internal ³)10,2 kPa10,2 kPa15,0 kPa15,0 kPa25,1 kPa25,1 kPa23,1 kPa23,1 kPa29,7 kPa39,9 kPa39,9 kPa49,4 kPa49,4 kPa
Medium volume cooling coil / heating coil1,3 l1,3 l1,3 l1,3 l1,3 l1,3 l1,8 l1,8 l2,1 l3,2 l3,2 l3,2 l3,2 l
Dimensions ceiling cassette h/b/t258/580/580 mm258/580/580 mm258/580/580 mm258/580/580 mm258/580/580 mm258/580/580 mm298/580/580 mm298/580/580 mm298/580/1110 mm298/580/1110 mm298/580/1110 mm298/580/1110 mm298/580/1110 mm
Dimensions grille h/w/d50/600/600 mm50/600/600 mm50/600/600 mm50/600/600 mm50/600/600 mm50/600/600 mm50/600/600 mm50/600/600 mm50/600/1200 mm50/600/1200 mm50/600/1200 mm50/600/1200 mm50/600/1200 mm
Weight31 kg31 kg31 kg31 kg31 kg31 kg34 kg34 kg63 kg64 kg64 kg64 kg64 kg
Series colorweiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß. ähnl. RAL 9010 weiß. ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010 weiß, ähnl. RAL 9010

Accessories / Spare parts

Variant
Loading ...
Für dieses Gerät stehen kein Ersatzteile zur Verfügung.

Downloads

Variant
Language
Pictures
REMKO KWD 25 EC Coanda jpg, 1,794,437,000.0
Assembly drawings
REMKO KWD 25 EC Coanda jpg, 100,544,000.0

Cooling load calculation for air-conditioners

The following rule of thumb applies when calculating the cooling capacity:
Approximately 30 W of cooling capacity are required per cubic meter. The cooling capacity for a room with a surface area of 28 m2 and height of 2.5 m can be calculated as follows:

28 m2 x 2,5 m x 30 W/m3 = 2.100 Watt (2,1 kW)

We recommend that you always calculate the cooling capacity for the room precisely.

Cooling load calculation Calculate required cooling capacity