KWE ECO SERIES - Bild 69791 KWE ECO SERIES - Bild 69792 KWE ECO SERIES - Bild 69793

REMKO KWE ECO SERIES Chillers for cooling

Variant EDV-Nr. Nominal cooling capacity
KWE 290 Eco 1704290 28,7 kW
KWE 330 Eco 1704330 32,7 kW
KWE 380 Eco 1704380 37,7 kW
KWE 430 Eco 1704430 42,5 kW
KWE 500 Eco 1704500 50,0 kW
KWE 550 Eco 1704550 55,3 kW
KWE 640 Eco 1704640 64,1 kW
KWE 730 Eco 1704730 73,2 kW
KWE 800 Eco 1704800 79,3 kW
KWE 970 Eco 1704970 97,2 kW
KWE 1060 Eco 1705060 106,4 kW
KWE 1150 Eco 1705150 115,9 kW
KWE 1240 Eco 1705240 123,9 kW
KWE 1320 Eco 1705320 132,6 kW
KWE 1400 Eco 1705400 140,5 kW
KWE 1480 Eco 1705480 148,3 kW
KWE 1550 Eco 1705550 155,3 kW
KWE 1600 Eco 1705600 161,3 kW
KWE 1850 Eco 1705850 186,2 kW
KWE 2100 Eco 1706100 211,4 kW
KWE 2350 Eco 1706350 233,7 kW
KWE 2600 Eco 1706600 260,2 kW
KWE 2850 Eco 1706850 286,8 kW
KWE 3150 Eco 1707150 315,2 kW

Variant

REMKO KWE ECO SERIES Chillers for cooling

The air-cooled chillers of the KWE Eco series in the power range from 28.7 to 315.2 kW can be individually configured for any application thanks to their modular design. In the hermetically sealed system of the chiller for outdoor installation, the innovative and climate-friendly refrigerant R452B is used. The selection of pumps in various pressure ratings allows the hydraulic components to be individually adapted to the respective application.

The pressure gauges already installed ex works in the hydraulic circuit and the accessibility of the essential hydraulic components via the opening of the swivelling control cabinet facilitate installation and commissioning, thus ensuring maximum service friendliness. In addition, thanks to the selection of state-of-the-art components and the optimisation of all device parameters, the devices already comply with the energy requirements of the more stringent Eco-Design Directive from 01/01/2021.

  • Hydraulic components individually configurable
  • Easy access to the essential device components
  • Future-proof thanks to climate-friendly refrigerant R452B
  • Optional components to reduce noise emissions available
  • Integration into an existing building control system possible
  • Units already ErP-compliant according to the more stringent Eco-Design Directive as of 01/01/2021

Technical data

Variant KWE 290 Eco KWE 330 Eco KWE 380 Eco KWE 430 Eco KWE 500 Eco KWE 550 Eco KWE 640 Eco KWE 730 Eco KWE 800 Eco KWE 970 Eco KWE 1060 Eco KWE 1150 Eco KWE 1240 Eco KWE 1320 Eco KWE 1400 Eco KWE 1480 Eco KWE 1550 Eco KWE 1600 Eco KWE 1850 Eco KWE 2100 Eco KWE 2350 Eco KWE 2600 Eco KWE 2850 Eco KWE 3150 Eco
Nominal cooling capacity 28,7 kW 32,7 kW 37,7 kW 42,5 kW 50,0 kW 55,3 kW 64,1 kW 73,2 kW 79,3 kW 97,2 kW 106,4 kW 115,9 kW 123,9 kW 132,6 kW 140,5 kW 148,3 kW 155,3 kW 161,3 kW 186,2 kW 211,4 kW 233,7 kW 260,2 kW 286,8 kW 315,2 kW
Energy efficiency ratio EER 2,9 3,1 3,0 3,3 3,6 3,3 3,0 3,2 2,8 3,3 3,2 3,0 3,0 3,1 3,2 3,1 3,1 3,1 3,3 3,2 3,2 3,1 3,0 2,9
SEER 4,1 4,1 4,1 4,7 5,1 4,7 4,7 5,2 4,8 5,4 5,5 4,8 4,8 4,9 5,0 4,9 4,9 4,9 5,3 5,3 5,3 5,4 5,3 5,2
Degree of effective use of room cooling 163 % 162 % 164 % 181 % 194 % 181 % 181 % 201 % 182 % 208 % 212 % 184 % 182 % 188 % 192 % 187 % 183 % 187 % 203 % 205 % 205 % 209 % 204 % 202 %
Cooling return adjusting range +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C +5 bis +18 °C
Operating range, cooling +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C +5 bis +48 °C
Operating range, cooling (expansion) -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C -15 bis +48 °C
Number of cooling circuits 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Refrigerant R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B R452B
GWP value 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676 676
Refrigerant, basic capacity 13,0 kg 13,5 kg 14,00 kg 16,0 kg 8,5 kg 9,0 kg 9,0 kg 10,0 kg 10,0 kg 12,5 kg 12,5 kg 13,0 kg 13,5 kg 13,5 kg 14,0 kg 14,5 kg 15,0 kg 18,0 kg 18,0 kg 18,5 kg 19,0 kg 21,0 kg 22,0 kg 22,5 kg
CO2 Equivalent 8,79 t 9,13 t 9,46 t 10,82 t 5,75 t 6,08 t 6,08 t 6,76 t 6,76 t 8,45 t 8,45 t 8,79 t 9,13 t 9,13 t 9,46 t 9,80 t 10,14 t 12,17 t 12,17 t 12,51 t 12,84 t 14,20 t 14,87 t 15,21 t
Compressor, number/type 1 / Scroll 1 / Scroll 1 /Scroll 2/Scroll 2/Scroll 2/ Scroll 2/Scroll 2/Scroll 2/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll 4/Scroll
Air volume max. 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 19.500 m³/h 28.000 m³/h 39.000 m³/h 39.000 m³/h 39.000 m³/h 39.000 m³/h 39.000 m³/h 39.000 m³/h 39.000 m³/h 58.500 m³/h 58.500 m³/h 58.500 m³/h 58.500 m³/h 78.000 m³/h 83.600 m³/h 83.600 m³/h
Number of fans 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 4 4 4
Sound pressure level 47,2 dB(A) 48,5 dB(A) 49,7 dB(A) 51,2 dB(A) 50,6 dB(A) 55,4 dB(A) 55,4 dB(A) 55,2 dB(A) 55,2 dB(A) 52,6 dB(A) 57,3 dB(A) 57,2 dB(A) 58,1 dB(A) 58,1 dB(A) 58,8 dB(A) 58,8 dB(A) 58,8 dB(A) 60,0 dB(A) 60,2 dB(A) 60,5 dB(A) 60,8 dB(A) 61,5 dB(A) 61,5 dB(A) 61,5 dB(A)
Soundpower level 78,9 dB(A) 80,2 dB(A) 81,4 dB(A) 82,9 dB(A) 82,3 dB(A) 87,1 dB(A) 887,1 dB(A) 86,8 dB(A) 86,8 dB(A) 84,4 dB(A) 89,1 dB(A) 89,1 dB(A) 90,0 dB(A) 90,0 dB(A) 90,7 dB(A) 90,7 dB(A) 90,7 dB(A) 92,0 dB(A) 92,2 dB(A) 92,5 dB(A) 92,8 dB(A) 93,7 dB(A) 93,7 dB(A) 93,7 dB(A)
Voltage supply 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz 400/3~N/50 V/Ph/Hz
Protection class IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4 IP X4
Electrical nominal power consumption, cooling 7,7 kW 9,1 kW 10,0 kW 12,7 kW 14,0 kW 16,8 kW 20,2 kW 22,6 kW 26,3 kW 28,6 kW 33,4 kW 37,0 kW 42,0 kW 43,0 kW 44,0 kW 48,1 kW 52,1 kW 51,9 kW 56,2 kW 62,7 kW 70,3 kW 79,7 kW 91,7 kW 103,8 kW
Electrical nominal current consumption, cooling 14,0 A 16,4 A 18,1 A 23,0 A 25,2 A 30,4 A 36,4 A 40,8 A 47,5 A 51,6 A 60,3 A 66,8 A 75,8 A 77,6 A 79,5 A 86,8 A 94,1 A 93,8 A 101,4 A 113,2 A 127,0 A 143,9 A 165,7 A 187,4 A
Operation pressure max. agent 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa 800 kPa
Nominal volume flow rate of medium, cooling 5,1 m³/h 5,9 m³/h 6,6 m³/h 7,3 m³/h 8,6 m³/h 9,5 m³/h 11,0 m³/h 12,6 m³/h 13,8 m³/h 16,2 m³/h 17,7 m³/h 20,0 m³/h 21,3 m³/h 22,8 m³/h 24,2 m³/h 25,5 m³/h 26,7 m³/h 27,7 m³/h 32,0 m³/h 36,6 m³/h 40,1 m³/h 44,6 m³/h 49,2 m³/h 54,1 m³/h
Pipe connection, medium-side inlet/outlet 1 1/2 inch 1 1/2 inch 1 1/2 inch 1 1/2 inch 2 inch 2 inch 2 inch 2 inch 2 inch 2 1/2 inch 2 1/2 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 100 inch DN 100 inch DN 100 inch
Medium connections 1 1/2 inch 1 1/2 inch 1 1/2 inch 1 1/2 inch 2 inch 2 inch 2 inch 2 inch 2 inch 2 1/2 inch 2 1/2 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 80 inch DN 100 inch DN 100 inch DN 100 inch
Dimsensions h/w/d 2030/1100/1200 mm 2030/1100/1200 mm 2030/1100/1200 mm 2030/1100/1200 mm 2150/1100/1200 mm 2150/1100/1200 mm 2150/1100/1200 mm 2200/1050/1400 mm 2200/1050/1400 mm 2140/1100/2150 mm 2140/1100/2150 mm 1800/1100/3470 mm 1800/1100/3470 mm 1800/1100/3470 mm 1800/1100/3470 mm 1800/1100/3470 mm 1800/1100/3470 mm 1800/1100/4370 mm 1800/1100/4370 mm 1800/1100/4370 mm 1800/1100/4370 mm 2100/1100/5300 mm 2100/1100/5300 mm 2100/1100/5300 mm
Weight 343 kg 345 kg 360 kg 415 kg 435 kg 455 kg 455 kg 615 kg 620 kg 962 kg 968 kg 1.048 kg 1.069 kg 1.096 kg 1.343 kg 1.354 kg 1.365 kg 1.650 kg 1.750 kg 1.805 kg 1.865 kg 2.154 kg 2.205 kg 2.265 kg
Serial colour ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018 ähnlich RAL 9018

Accessories / Spare parts

Variant
Loading ...
Für dieses Gerät stehen kein Ersatzteile zur Verfügung.

Downloads

Variant
Language

CheckServ - Customer service

For technical equipment handover, maintenance and completion of the air conditioning systems, you can add in the service CheckServ. REMKO supports you from planning to technical device handover to maintenance. This complete chain of services makes it easy to install even complex air conditioning systems.

CheckServ Technical equipment handover and maintenance

CheckServ