RVS DC SERIES - Bild 57023 RVS DC SERIES - Bild 57024

REMKO RVS DC SERIES Chillers for cooling and heating

Variant EDV-Nr. Cooling capacity
RVS 50 DC 1611692 4,7 (1,6-5,6) kW
RVS 80 DC 1611693 7,6 (2,0-10,0) kW
RVS 130 DC 1611694 13,5 (5,0-14,5) kW
RVS 180 DC 1611695 16,9 (7,0-20,0) kW
RVS 220 DC 1611677 19,3 (8,5-22,0) kW
RVS 260 DC 1611679 22,5 (10,3-26,0) kW

Variant

REMKO RVS DC SERIES Chillers for cooling and heating

With inverter technology

The units of the RVS 50-260 DC series, with an output range between 4.7 and 22.5 kW, are particularly quiet, air-cooled chillers for outdoor installation. Due to the standard heat pump function, the units can be used for both cooling and heating.

During cooling, the application limits of the units lie at -15°C, whereby the units are also suitable for process applications that have to be cooled throughout the year. Both the inverter condenser used and the infinitely variable expansion valve guarantee a needs-based adaptation of the cooling capacity to the pertinent application conditions.

In addition, the units have state-of-the-art, energy-efficient EC fans in the standard version. These fans provide considerable cost savings in comparison with conventional AC technology, especially in the partial load range. The interaction from the optimisation of the heat exchanger surfaces, use of highly efficient components and the optimisation of all operation-related system parameters ensures that the units have a very high degree of efficiency and therefore correspond with the pertinent requirements of the Eco-Design Directive.

In addition, the devices are available in a special low-temperature version in which particularly low medium inlet temperatures of -2°C can be implemented.

  • Variable power control thanks to the inverter condenser and electronic expansion valve
  • Floating switch contacts for integration into a building control system
  • State-of-the-art touchpad in an IP54 housing for easy operation
  • Application of cooling mode up to -15°C in the standard version
  • Low temperature version for low inlet temperatures optionally available
  • Heating operation thanks to EVI injection down to -30 °C outside temperature (RVS 220-260 DC)
  • Units are ErP-compliant according to the Eco-Design Directive as of 01/01/2021 (RVS 80-260 DC)

Technical data

VariantRVS 50 DCRVS 80 DCRVS 130 DCRVS 180 DCRVS 220 DCRVS 260 DC
Nominal cooling capacity4,7 (1,6-5,6) kW7,6 (2,0-10,0) kW13,5 (5,0-14,5) kW16,9 (7,0-20,0) kW19,3 (8,5-22,0) kW22,5 (10,3-26,0) kW
SEER3,88 4,33 5,01 4,15 4,15 4,15
Degree of effective use of room cooling152 %170 %195 %163 %163 %163 %
Heating capacity (heating coil)4,3 (2,0-6,8) kW8,5 (2,5-10,8) kW12,3 (5,0-17,3) kW18,0 (7,0-25,1) kW26,0 (9,5-27,3) kW28,2 (11,0-31,5) kW
Cooling return adjusting range+10 bis +20 °C+10 bis +20 °C+10 bis +20 °C+10 bis +20 °C+7 bis +25 °C+7 bis +25 °C
Operating range, cooling-15 bis +45 °C-15 bis +45 °C-15 bis +45 °C-15 bis +45 °C-15 bis +45 °C-15 bis +45 °C
Heating return adjusting range+30 bis +50 °C+30 bis +50 °C+30 bis +50 °C-15 bis +45 °C+25 bis +60 °C+25 bis +60 °C
Operating range, heating-20 bis +52 °C-20 bis +52 °C-20 bis +52 °C-20 bis +52 °C-30 bis +43 °C-30 bis +43 °C
Number of cooling circuits1 1 1 1 1 1
RefrigerantR410A R410A R410A R410A R410A R410A
GWP value2088 2088 2088 2088 2088 2088
Refrigerant, basic capacity1,7 kg2,4 kg3,2 kg4,4 kg4,5 kg5,0 kg
CO2 Equivalent3,55 t5,01 t6,68 t9,19 t9,40 t10,44 t
Air volume max.3900 m³/h3900 m³/h7800 m³/h8600 m³/h13.000 m³/h15.000 m³/h
Number of fans1 1 2 2 2 2
Sound pressure level37,3 dB(A)37,3 dB(A)41,7 dB(A)46,2 dB(A)47,0 dB(A)48,0 dB(A)
Soundpower level68,5 dB(A)68,5 dB(A)73,1 dB(A)77,6 dB(A)78,0 dB(A)79,0 dB(A)
Voltage supply230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz230/1~/50 V/Ph/Hz400/3~/50 V/Ph/Hz400/3~/50 V/Ph/Hz400/3~/50 V/Ph/Hz
Protection classIP X4 IP X4 IP X4 IP X4 IP X4 IP X4
Electrical nominal power consumption, cooling1,3 kW2,3 kW4,5 kW5,5 kW7,8 kW9,0 kW
Electrical nominal current consumption, cooling5,6 A10,4 A20,7 A9,5 A13,3 A14,9 A
Operation pressure max. agent600 kPa600 kPa600 kPa600 kPa600 kPa600 kPa
Nominal volume flow rate of medium, cooling1,00 m³/h1,60 m³/h2,80 m³/h4,20 m³/h3,2 m³/h3,6 m³/h
Min. medium flow0,62 m³/h1,00 m³/h1,75 m³/h2,63 m³/h2,4 m³/h2,8 m³/h
Maximum volume flow medium1,68 m³/h2,70 m³/h4,70 m³/h7,00 m³/h6,3 m³/h7,4 m³/h
Max. pump outlet pressure51 kPa99 kPa101 kPa150 kPa84 kPa125 kPa
Pipe connection, medium-side inlet/outlet1 inch1 inch1 1/4 inch1 1/4 inch1 1/4 inch1 1/4 inch
Medium connections1 inch1 inch1 1/4 inch1 1/4 inch1 1/2 inch1 1/2 inch
Dimsensions h/w/d787/1045/459 mm900/980/465 mm1320/990/395 mm1588/1175/400 mm1600/1175/400 mm1600/1175/400 mm
Weight95,0 kg110,0 kg148,0 kg219,0 kg206,0 kg240,0 kg
Serial colourähnlich RAL 9010 ähnlich RAL 9010 ähnlich RAL 9010 ähnlich RAL 9010 ähnlich RAL 9010 ähnlich RAL 9010

Accessories / Spare parts

Variant
Loading ...
Loading ...

Downloads

Variant
Language
Pictures
REMKO RVS 50 DC jpg, 485,783,000.0
Logos
REMKO RVS 50 DC jpg, 152,032,000.0
REMKO RVS 50 DC jpg, 126,470,000.0

CheckServ - Customer service

For technical equipment handover, maintenance and completion of the air conditioning systems, you can add in the service CheckServ. REMKO supports you from planning to technical device handover to maintenance. This complete chain of services makes it easy to install even complex air conditioning systems.

CheckServ Technical equipment handover and maintenance